Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/21/2015 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 05/21/2015 |
PLUMBING - INTERMEDIATE |
|
Approved |
ADD SAFETY STRAPS |
| 05/05/2015 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 05/05/2015 |
PLUMBING - INTERMEDIATE |
|
Denied |
INTERCEPTOR REQUIRES PROPER SIZING AND A VENT. FLOW CONTROL VENT, INTERCEPTOR, AND FIXTURE (FS) VENTS SHALL RISE VERTICALLY TO 6" ABOVE FLOOD LEVEL PRIOR TO OFFSET. TIE-IN AND DRAW FROM GT LOCATIONS OK, UNLESS CHANGING SIZE. INTERCEPTOR AND ANY CHANGES REQUIRES PLAN REVIEW |