Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T15CM01551
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/05/2015 | FIRE SPKLR - FINAL | Approved | ||
07/29/2015 | FIRE SPKLR - FINAL | Partial Approval | 1. Upright in overhead over mens bathroom is blocked by domestic water pip. 2. insulation is blocking 3 heads ( uprgihts ) over merchandise floor. 3. drop ceiling tiles are not in place |