Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T15CM01425
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2015 | FIRE - FINAL | Approved | ||
09/04/2015 | FIRE - FINAL | Partial Approval | PARTIAL APPROVAL 1. label electric panel 2. repair/replace ceiling tiles in bathroom and training office 3. exit sign must show arrow 4. remove thumbolts on exit door ( that are additional to lock) and remplace with blanks. |
|
05/18/2015 | FIRE - FINAL | Denied | Sprinkler drops in pool area OKAY to install drop ceiling tiles Need to add sprinkler coverage under new platform for pool anything over 48 inches wide shall have sprinkler coverage. Platform size is 21 feet long by 52 inches wide. |