Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T15CM01425
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/04/2015 | FIRE SPKLR - FINAL | Approved | drops added to pool area per code. | |
05/18/2015 | FIRE SPKLR - FINAL | Denied | Sprinkler drops in pool area OKAY to install drop ceiling tiles Need to add sprinkler coverage under new platform for pool anything over 48 inches wide shall have sprinkler coverage. Platform size is 21 feet long by 52 inches wide. |