Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2015 | PLUMBING - GAS PRESS TEST FNL | Approved | IVRS - Inspection :* | |
| 03/02/2015 | PLUMBING - GAS PRESS TEST FNL | Approved | 14 PSI TEST IS OK | |
| 02/26/2015 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/26/2015 | PLUMBING - GAS PRESS TEST FNL | Denied | 1/2" GAS PIPE 56' FROM METER NOT ADEQUATE FOR 75,000 BTU FURNACE. PROVIDE MIN 10 PSI TEST. TERMINATE CONDENSATE TO THE SCUPPER AT FRONT OF HOUSE. BLOCK & CLAMP PVC EVERY 4'. |