Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/04/2015 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 03/02/2015 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/02/2015 | PLUMBING - FINAL | Denied | CORRECT WH & FURNACE VENTING; B-VENT REQUIRES PROPER DIRECTION OF FLOW & CLEARANCE FROM COMBUSTIBLES. RELIEF VALVE MAY NOT BE TRAPPED. CO DETECTORS REQUIRED. SECURE PIPING. | |
| 02/26/2015 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/24/2015 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |