Inspection Status: Passed
Inspection History: COT - RSEL - Service Upgrade
| Date |
Description |
Inspector |
Results |
Comments |
| 02/14/2020 |
COT - RSEL - Service Upgrade |
DQUINN |
Approved |
Entered by DQUINN1 - RVI |
| 08/31/2017 |
COT - RSEL - Service Upgrade |
mpugh1 |
Not ready for Inspection |
Entered by MPUGH1 - complete elec. @ shop, provide city plans, protect conducters within 8' of grade, bring equipment grounding conductor to new house panel, provide ground rods and gas/water bond at house panel, isolate neutral at house panel, terminate all conducters at new sub- panel, provide disconnect at each building, incomplete inspection. |
| 03/14/2017 |
COT - RSEL - Service Upgrade |
mpugh1 |
Partial Approval |
Entered by MPUGH1 - line side only |
| 03/10/2017 |
COT - RSEL - Service Upgrade |
mpugh1 |
Not ready for Inspection |
Entered by MPUGH1 - |