Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSEL - Service Upgrade
Permit Number - T15CM01074
Inspection Description - COT - RSEL - Service Upgrade
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2020 | COT - RSEL - Service Upgrade | DQUINN | Approved | Entered by DQUINN1 - RVI |
08/31/2017 | COT - RSEL - Service Upgrade | mpugh1 | Not ready for Inspection | Entered by MPUGH1 - complete elec. @ shop, provide city plans, protect conducters within 8' of grade, bring equipment grounding conductor to new house panel, provide ground rods and gas/water bond at house panel, isolate neutral at house panel, terminate all conducters at new sub- panel, provide disconnect at each building, incomplete inspection. |
03/14/2017 | COT - RSEL - Service Upgrade | mpugh1 | Partial Approval | Entered by MPUGH1 - line side only |
03/10/2017 | COT - RSEL - Service Upgrade | mpugh1 | Not ready for Inspection | Entered by MPUGH1 - |