Permit: T15CM01052

Parcel: 137030230

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/21/2015 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/19/2015 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
04/15/2015 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/15/2015 ELECTRIC - SERVICE UPGRADE Denied 1. PERMIT FOR 200 AMP INCREASE ONLY 100 AMP SERVICE INSTALLED
2. METAL ADDRESS TAG METER BASE
3. GROUND RODS AND RISER CLAMPS OK
4. AFTER CROSSOVER
**REVISE PERMIT TO 100 AMP OR BUILD TO PLAN**
04/07/2015 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
04/07/2015 ELECTRIC - SERVICE UPGRADE Not ready for Inspection 1. PROVIDE MAST/RISER WITH 2 POINTS OF ATTACHMENT TO BUILDING
2. 2 GROUND RODS REQUIRED MINIMUM 6' APART