Permit: T15CM01033

Parcel: 133200240

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/24/2015 PLUMBING - FINAL Approved IVRS - Inspection :*
08/20/2015 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
08/20/2015 PLUMBING - FINAL Partial Approval CAULK TOILETS AND SINKS. CONDENSOR IS OVERFUSED. PAINT EXPOSED ARMAFLEX. PROVIDE TAMPER-PROOF CAPS. COMBUSTION AIR MIN 40 SQ IN EACH. PROVIDE ADEQUATE COMBUSTION AIR HIGH AND LOW FOR WATER HEATER. USE A REDUCER AT WATER HEATER VENT CONNECTOR. PROVIDE A TRAP AND OVERFLOW SENSOR AT A/C COILS. PROVIDE VACUUM BREAKERS AT HOSE BIBS.