Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/05/2015 |
BUILDING ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 05/05/2015 |
BUILDING ABOVE CEILING |
|
Approved |
CEILING DIFFUSERS NOT PER PLAN DETAIL. PLANS REQUIRE RIGID ELBOWS PRIOR TO CONNECTION TO DIFFUSER WITH FLEX. PLANS SHOW DIFFUSERS TO BE ADJUSTABLE. FINISH ELECTRICAL ABOVE CEILING. WILL CHECK ON FINAL. PROVIDE AIR BALANCE REPORT ON FINAL. PROVIDE A TIME CLOCK FOR BATHROOM EXHAUST |