Permit: T15CM00949

Parcel: 140260380

Inspection Status: Approved

Inspection History: SITE - SEWER

Permit Number - T15CM00949

Inspection Description - SITE - SEWER

Inspection Status - Approved

Date Description Inspector Results Comments
12/04/2015 SITE - SEWER Approved MANDREL PULL TEST HAS BEEN PROVIDED ON M.H. #1 TO M.H. #2
AIR PRESSURE TEST HAS BEEN PROVIDED BETWEEN M.H. #2 TO M.H. #3 AND M.H. #3 TO #4
12/02/2015 SITE - SEWER Denied IVRS - Inspection :23No Description.| 99946
*
11/12/2015 SITE - SEWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/29/2015 SITE - SEWER Partial Approval THE CREW CALLED ME AT 10:30 AND ADVISED ME THAT THE CONES WILL BE INSTALLED BY LUNCH TIME. I REINSPECTED THE AREA ABOUT 13:30 AND APPROVED THE MANHOLES FOR BACKFILL PLACEMENT.
10/29/2015 SITE - SEWER Not ready for Inspection LOOKING AT MANHOLES #2, #3, #4, 2 STACKS HAVE BEEN PLACED BUT THE FINAL CONE IS NOT IN PLACE AT THIS TIME. ADVISED THE CONTRACTOR TO EITHER RESCHEDULE ANOTHER INSPECTION OR CALL ME LATER TODAY IF THEY ARE INSTALLED. BACKFILL PLACEMENT CANNOT BE DONE TILL THE CONES HAVE BEEN INSTALLED. IT IS 9:30 AT THIS TIME.
09/17/2015 SITE - SEWER Partial Approval 1. FINAL CONNECTION TO M.H #6 OKAY
2. OKAY TO BACKFILL TRENCH
09/03/2015 SITE - SEWER Partial Approval IVRS - Inspection :*
09/03/2015 SITE - SEWER Partial Approval 1. 8" SDR-35 SITE SEWER FROM MANHOLE #6 TO MANHOLE #5 OKAY AS NOTED ON PLAN
2. 8" SDR-35 SITE SEWER FROM MANHOLE #5 TO MANHOLE #2 OKAY
3. TRACER WIRE PROVIDED
4. SHALL PROVIDE AN AIR PRESSURE TEST AT A LATER DATE. 5 PSI MIN TEST
5. OKAY TO COVER AT OWN RISK
6. NOTE: SHALL CALL FOR INSPECTION WHEN MANHOLE BASE HAS BEEN POURED
09/02/2015 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
09/02/2015 SITE - SEWER Not ready for Inspection NO TRACE WIRE AT PIPE TO BE INSPECTED