Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2015 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/21/2015 | MECHANICAL - FINAL | Denied | 1/2" GAS LIE NOT ADEQUATE FOR 100,00 BTU. FURNACE 40 + FEET FROM METER. USE 3/4". REMOVE THE TRAP FROM CONDENSATE LINE. PROVIDE MIN R8 DUCT LINER. |