Permit: T15CM00873

Parcel: 12615011C

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T15CM00873

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
03/04/2015 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
03/04/2015 PLUMBING - ROUGH, SOIL Approved CORRECTIONS HAVE BEEN MADE. OK TO BACKFILL & POUR SLAB
02/26/2015 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/26/2015 PLUMBING - ROUGH, SOIL Denied 3" CONN REQ AT WASHER DRAIN. 3" WASTE REQ 3" CO. FURNCO COUPLINGS NOT LISTED FOR INSDIE OF BUILDING. LISTED TRANSITION COUPLINGS REQ AT C1 TO P1. INSTALL FUTURE TEST FITTINGS WHEN TESTING IN SECTIONS. DRY VENT SHALL RISE VERTICALLY & 6" ABOVE FLOOD LEVEL