Permit: T15CM00873

Parcel: 12615011C

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T15CM00873

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2015 BUILDING - FINAL Approved
04/27/2015 BUILDING - FINAL Partial Approval IVRS - Inspection :*
04/27/2015 BUILDING - FINAL Partial Approval PROVIDE MIXING VALVES AS PER PLANS. PROVIDE HAMMER ARRESTORS. PROVIDE AIR BALALNCE REPORT. FLUSH HANDLES ON WRONG SIDE AT ADA TOILETS. NO FLEX DUCT ALLOWED FOR DRYER EXHAUST. ADD NEW SINK AND PIPING TO PLANS