Permit: T15CM00855

Parcel: 14118611A


Addresses:

9046 S HOUGHTON RD

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
07/29/2015 FIRE - ALARM FINAL Approved
07/28/2015 FIRE - ALARM FINAL Partial Approval the 24 hour test of batteries was invalidated when the electrician removed tape and turned the breaker to alarm on again.

PERFORMING 2ND TEST OF BATTERIES . Began at 2:50 PM on 7/28/15 - will need to do an alarm ( pull station test) after 24 hrs to verify batteries operated.
07/24/2015 FIRE - ALARM FINAL Partial Approval ALREADY PASSED FLOW 31 SECONDS TO ALARM, TAMPER, SMOKE, PULL
VERIFIED SIGNALS.
STILL NEEDS 24 HR TEST ON BATTERY POWER ONLY ( BATTERIES WERE LOW AFTER THE FIRST 4 TESTS COMPLETED)
AC OFF - SIGNALS WERE NOT VERIFIED CORRECTLY.