Inspection History: FIRE - ALARM FINAL
Permit Number - T15CM00855
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/29/2015 | FIRE - ALARM FINAL | Approved | ||
07/28/2015 | FIRE - ALARM FINAL | Partial Approval | the 24 hour test of batteries was invalidated when the electrician removed tape and turned the breaker to alarm on again. PERFORMING 2ND TEST OF BATTERIES . Began at 2:50 PM on 7/28/15 - will need to do an alarm ( pull station test) after 24 hrs to verify batteries operated. |
|
07/24/2015 | FIRE - ALARM FINAL | Partial Approval | ALREADY PASSED FLOW 31 SECONDS TO ALARM, TAMPER, SMOKE, PULL VERIFIED SIGNALS. STILL NEEDS 24 HR TEST ON BATTERY POWER ONLY ( BATTERIES WERE LOW AFTER THE FIRST 4 TESTS COMPLETED) AC OFF - SIGNALS WERE NOT VERIFIED CORRECTLY. |