Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T15CM00752
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2015 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/08/2015 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 05/08/2015 | ELECTRIC - ABOVE CEILING | Partial Approval | 1. PROVIDE PROPER FLEX SUPPORT 2. PROVIDE SEISMIC SUPPORT ON REGISTERS 3. PROVIDE SEISMIC SUPPORT ON LIGHTS 4. PROVIDE CONSTRUCTION SCREWS AT STRUCTURAL, NOT SHEETROCK SCREWS (NOT RATED) 5. PROVIDE FULL RADIUS BENDS ON FLEX DUCT 6. PROVIDE SUPPORT OF ELEC ??? 7. SEAL DUCTS |