Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2015 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/08/2015 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 05/08/2015 | ELECTRIC - ABOVE CEILING | Partial Approval | 1. PROVIDE PROPER FLEX SUPPORT 2. PROVIDE SEISMIC SUPPORT ON REGISTERS 3. PROVIDE SEISMIC SUPPORT ON LIGHTS 4. PROVIDE CONSTRUCTION SCREWS AT STRUCTURAL, NOT SHEETROCK SCREWS (NOT RATED) 5. PROVIDE FULL RADIUS BENDS ON FLEX DUCT 6. PROVIDE SUPPORT OF ELEC ??? 7. SEAL DUCTS |