Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2015 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/27/2015 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/27/2015 | ELECTRIC - FINAL | Denied | PROVIDE A GROUNDING ELECTRODE SYSTEM WITH NO SPLICES IN THE CONDUCTOR. THE PANEL IS NOT ADEQUATELY SECURED TO THE WALL. PROVIDE A PANEL SCHEDULE | |
| 02/25/2015 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 02/25/2015 | ELECTRIC - FINAL | Partial Approval | PROVIDE 2 GROUND RODS MIN 6' APART. OK TO USE EXISTING UFER UNTIL NEW ELECTRODES ARE INSTALLED RECALL FOR FINAL AFTER FINAL CONNECTIONS |