Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T15CM00730
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2015 | FIRE - FINAL | Approved | ||
04/14/2015 | FIRE - FINAL | Denied | 1. FDC one swivel hard to turn need to repair or replace 2. Label breakers in panel 3. Need power on to test all back up lighting 4. Need annual sprinkler inspection done pass due 5. Need 5 year check valve inspection done 6. Need riser room key installed in the F.D. key box |
|
04/10/2015 | FIRE - FINAL | Denied | 1. Storage/utility dllors handle is on backwards ( person could use keyed lock on inside, so would require Key to get out). 2. No pressure on Riser supply side guage 3. Main shutoff valve is in on position, but not locked out and not supervised. |