Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/16/2015 | FIRE SPKLR - FINAL | Approved | ||
| 04/14/2015 | FIRE SPKLR - FINAL | Denied | 1. FDC one swivel hard to turn need to repair or replace 2. Need annual sprinkler inspection done pass due 3. Need 5 year check valve inspection done 4. Need riser room key installed in the F.D. key box |
|
| 04/10/2015 | FIRE SPKLR - FINAL | Denied | 2. No pressure on Riser supply side guage 3. Main shutoff valve is in on position, but not locked out and not supervised. 4. Need annual fire sprinkler system test and record of passing. |