Permit: T15CM00730

Parcel: 133231420


Addresses:

7713 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
04/16/2015 FIRE SPKLR - FINAL Approved
04/14/2015 FIRE SPKLR - FINAL Denied 1. FDC one swivel hard to turn need to repair or replace
2. Need annual sprinkler inspection done pass due
3. Need 5 year check valve inspection done
4. Need riser room key installed in the F.D. key box
04/10/2015 FIRE SPKLR - FINAL Denied 2. No pressure on Riser supply side guage
3. Main shutoff valve is in on position, but not locked out and not supervised.
4. Need annual fire sprinkler system test and record of passing.