Inspection History Details
Inspection Status: Denied
Inspection History: FIRE SPKLR - FINAL
Permit Number - T15CM00729
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/14/2015 | FIRE SPKLR - FINAL | Denied | 1. FDC one swivel hard to turn need to repair or replace 2. Need annual sprinkler inspection done pass due 3. Need 5 year check valve inspection done 4. Need riser rom key installed in the F.D. key box |
|
04/10/2015 | FIRE SPKLR - FINAL | Denied | 1. Sprinkler coverage in receiving/storage area has a head blocked by falling ceiling. 2. No pressure on Riser supply side guage 3. Main shutoff valve is in on position, but not locked out and not supervised. 4. Need annual fire sprinkler system test and record of passing. |