Permit: T15CM00713

Parcel: 11103086E

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T15CM00713

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/21/2015 FIRE - FINAL Approved WORK PERFORMED WAS ONLY FOR HAND RAILING. STAIR RISE ISSUES DO NOT FALL UNDER THIS PERMIT. WILL CONTACT BUILDING OWNER.
07/31/2015 FIRE - FINAL Denied DENIED
per IFC 1009.7.2
Stair riser hieght may not exceed a max of 7 inches.
Building #1 where stair was replaced...riser height is 8 inches
Building # 2 on T15CM00733 -
Riser is 9 " at R side of top stair to the landing. Max of 7 Inches is allowed.