Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2015 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/27/2015 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/27/2015 | ELECTRIC - SERVICE UPGRADE | Denied | 1. ADDRESS LABEL MISSING 2. 2 GROUND RODS MISSING 3. GAS BOND MISSING 4. GROUNDING ELECTRODE TO BE BONDED ON BOTH ENDS |