Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T15CM00578
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2015 | FIRE - FINAL | Approved | ||
06/17/2015 | FIRE - FINAL | Partial Approval | PENDING SUBMITTAL OF FIRE ALARM AS-BUILD DRAWINGS SHOWING ONLY 1 DUCT DETECTOR ( NOT TWO) AND SHOWING SIGNALS REPORT FROM CONTROL PANEL TO MONITORING COMPANY AS SUPERVISORY AND NOT 'ZONE 2'. | |
06/12/2015 | FIRE - FINAL | Denied | 1. Post occupant load 2. Rear kitchen exit - no keyed locking mechanism allowed. 3. need sign on interior riser - room door 4. need sign on exterior door to kitchen "Riser Room Access" 5. sign on Electric Room 6. sign on service doors to electric room that read " This door blocked" 7. Mount extinguishers on walls. 8. Need lock box on Front entrance wall of building with keys to all doors in path of the sprinkler riser. 9. Step from the South exit door drops 7 inches. does not meet the landings at doors requirements of 2012 IFC 1008. 1.6 or floor elevation in 2013 IFC 1008.1.5 |