Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T15CM00578
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2015 | FIRE - KITCHEN EXH HOOD FINAL | Approved | PULL STATION AND LINK PASSED. ALL GAS AND ELECTRIC UNDER HOOD SHUT DOWN. MAKE UP AIR SHUT DOWN AND EXHAUST STAYED ON. ALL NOZZLES ARE WITHIN DESIGN PER PLANS. HOOD SYSTEM IS TIED INTO ALARM SYSTEM AND NOTIFICATION DEVICES ALL ACITIVATED AND ALARM WAS RECIEVED AT THE PANEL AND THE MONITORING COMPANY AS AN 'ALARM' WITH A RESET. |