Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T15CM00578

Parcel: 12701003R


Addresses:

4901 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T15CM00578

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2015 FIRE - KITCHEN EXH HOOD FINAL Approved PULL STATION AND LINK PASSED.
ALL GAS AND ELECTRIC UNDER HOOD SHUT DOWN.
MAKE UP AIR SHUT DOWN AND EXHAUST STAYED ON. ALL NOZZLES ARE WITHIN DESIGN PER PLANS. HOOD SYSTEM IS TIED INTO ALARM SYSTEM AND NOTIFICATION DEVICES ALL ACITIVATED AND ALARM WAS RECIEVED AT THE PANEL AND THE MONITORING COMPANY AS AN 'ALARM' WITH A RESET.