Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2015 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/23/2015 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/18/2015 | BUILDING - FINAL | Partial Approval | PROVIDE LAYARDS AT COOKING APPLIANCES WITH WHEELS PROVIDE DRAINS FOR SODA SINK. FINISH SUB PANEL. PROVIDE MIN 6" AT CRITICAL LEVEL AT FLUSH METERS. ADHESIVE TAPE NOT ALLOWED OUTDOORS ON LINE SET BACKFLOW CERTS OK NEED STERELIZATION. PROVIDE A COMPLETE AIR BALANCE ON CERTIFIED FORM |