Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/03/2015 |
MECHANICAL - INTERMEDIATE |
|
Approved |
|
| 02/26/2015 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* |
| 02/26/2015 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
ALUMA FLEX NOT ALLOWED AT KITCHEN EXHAUST. MUST BE SMOOTH INTERIOR. PROVIDE MIN 1/8" PER FT SLOPE ON ALL SECTIONS OF CONDENSATE DRAIN. SUPPORT EVERY 4' & PAINT WITH LATEX PAINT. FINISH ALL WORK ON UPPER ROOF. 14 PSI TEST ON GASLINE IS OK. OK TO INSULATE, SHEETROCK, & TAPE, EXCEPT AT KITCHEN VENT & KITCHEN BEAM. |