Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T15CM00336

Parcel: 10605145B


Addresses:

3739 N ORACLE RD


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T15CM00336

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/05/2015 FIRE SPKLR - FINAL Approved Sprinkler corrections made
Annual reports in and 5 year check valve in
04/24/2015 FIRE SPKLR - FINAL Denied DENIED
1.The annual inspection report shown was from 2011. Still need a current annual inspection of the sprinkler system including a 5 yr check valve inspection.
2. The wall that has been extended in suite 3739 has changed the sprinkler coverage in the back hallway to the stockroom and the stockroom itself. An existing wall that was there before the contractor began remodeling on this permit and was unfinished
( studs- no drywall backing on storage side) has also created insufficient coverage for a portion of the stock room as well. The heads are more than 7.5 feet off the wall ( closer to 9 feet). Have a licensed sprinkler installation contractor pull a separate permit for the work to be done ( more than 5 heads to be moved or added), have plans drawn up and submitted to Tucson Fire Systems Design for approval before the work begins.
NS - 4/24/15