Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T15CM00336
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2015 | FIRE SPKLR - FINAL | Approved | Sprinkler corrections made Annual reports in and 5 year check valve in |
|
04/24/2015 | FIRE SPKLR - FINAL | Denied | DENIED 1.The annual inspection report shown was from 2011. Still need a current annual inspection of the sprinkler system including a 5 yr check valve inspection. 2. The wall that has been extended in suite 3739 has changed the sprinkler coverage in the back hallway to the stockroom and the stockroom itself. An existing wall that was there before the contractor began remodeling on this permit and was unfinished ( studs- no drywall backing on storage side) has also created insufficient coverage for a portion of the stock room as well. The heads are more than 7.5 feet off the wall ( closer to 9 feet). Have a licensed sprinkler installation contractor pull a separate permit for the work to be done ( more than 5 heads to be moved or added), have plans drawn up and submitted to Tucson Fire Systems Design for approval before the work begins. NS - 4/24/15 |