Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2015 | ELECTRIC - RECONNECT | Correction Required | TEP unable to turn the service on on 1/23/15 due to notes from our troubleman: LEFT LOADSIDE CONDUCTORS ARE BURNT AND CORRODED ... NO MTR INSTALL UNTIL REPAIRS ARE COMPLETE. The customer will need to make repairs and will need a new CC. | |
| 01/28/2015 | ELECTRIC - RECONNECT | Partial Approval | FOR REINSPECTION | |
| 01/21/2015 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 01/13/2015 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/13/2015 | ELECTRIC - RECONNECT | Denied | - SECURITY LIGHTING BACK PORCH NOT TO CODE - SUBPANEL NEUTRALS & GROUND TIED TOGETHER (ISOLATE) GROUNDS & NEUTRALS, COLOR CODE NEUTRAL WHITE - ALL BEDROOMS NEED SMOKE DETECTORS |