Permit: T15CM00105

Parcel: 11106283D


Addresses:

3411 E GLENN ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/15/2015 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/07/2015 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
01/06/2015 ELECTRIC - FINAL Partial Approval UNIT3
OUTDOOR RECEPTACLES TO BE GFI PROTECTED ALL UNITS FILL IN OPENING IN SUB PANEL. SMOKE DETECTORS TO BE 3' FROM AIR VENTS
UNIT 2
PROVIDE SMOKE DETECTOR IN HALLWAY SMOKE DETECTORS TO BE 3' FROM AIR VENTS
UNIT3
SMOKE DETECTORS TO BE 3' FROM AIR VENTS