Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T15CM00077
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2017 | FRAMING | Approved | ||
06/30/2016 | FRAMING | Not ready for Inspection | ||
05/10/2016 | FRAMING | Partial Approval | SUITE 180 ONLY RESTROOM FRAMING OK TO COVER. DEMISING WALL BETWEEN 170 AND 180 IS INCOMPLETE (NO DRYWALL ON EITHER SIDE) |
|
04/08/2016 | FRAMING | Denied | PLASTIC BOXES NOT PERMITTED, PLAN SPECIFIES STEEL WITH STEEL BUSHINGS. ALL PENETRATIONS IN DEMISING WALLS MUST BE FIRE SEALED. |
|
04/08/2016 | FRAMING | Denied | 1. MANY DETAILS AND KEYNOTES ON PLANS DO NOT MATCH BUILDING. PROVIDE CLARIFICATION FROM ARCHITECT. 2. DRYWALL IN TRUSS WEBBING NOT SHOWN ON PLAN. PROVIDE CLARIFICATION FROM ARCHITECT. 3. TOP TRACK ON METAL STUD WALLS NOT ANCHORED PER PLAN. |
|
04/08/2016 | FRAMING | Not ready for Inspection | Unit #180 | |
04/08/2016 | FRAMING | Not ready for Inspection | ||
03/21/2016 | FRAMING | Partial Approval | IVRS - Inspection :* | |
06/18/2015 | FRAMING | Partial Approval | PARTITION BETWEEN 6 AND 7 OK TO SHEETROCK | |
04/29/2015 | FRAMING | Partial Approval | IVRS - Inspection :* | |
04/28/2015 | FRAMING | Partial Approval | UNITS 4 AND 5 | |
04/28/2015 | FRAMING | Partial Approval | UNIT'S 4 & 5 | |
04/13/2015 | FRAMING | Partial Approval | IVRS - Inspection :* | |
04/10/2015 | FRAMING | Partial Approval | ON 3 UNITS |