Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2015 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/04/2015 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/04/2015 | ELECTRIC - FINAL | Denied | 1. DEAD FRONT MISSING FROM ELECTRICAL PANEL 2. 14 AWG CONDUCTORS NOT ALLOWED UNDER 20 AMP BREAKER |
|