Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG PIPING FLUSH
Permit Number - T15BU01503
Inspection Description - FIRE SPKLR - UG PIPING FLUSH
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/09/2016 | FIRE SPKLR - UG PIPING FLUSH | Approved | ||
02/03/2016 | FIRE SPKLR - UG PIPING FLUSH | Not ready for Inspection | Had a 2 inch hose running off the 4 inch Fire Main for the flush. Need a 4 inch or wyed down to 2 2" hose. No burlap for catching debris. |