Inspection Status: Approved
Inspection History: FIRE SPKLR - UG PIPING FLUSH
| Date |
Description |
Inspector |
Results |
Comments |
| 02/09/2016 |
FIRE SPKLR - UG PIPING FLUSH |
|
Approved |
|
| 02/03/2016 |
FIRE SPKLR - UG PIPING FLUSH |
|
Not ready for Inspection |
Had a 2 inch hose running off the 4 inch Fire Main for the flush. Need a 4 inch or wyed down to 2 2" hose. No burlap for catching debris. |