Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T15BU01499

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2016 FIRE SPKLR - OH PIPING & HYDRO Approved All corrections have been made ( heads replaced and added per required on 5/12/16).
05/12/2016 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Hydro passed 200psi>2hrs
OH DENIED
1) Painted upright over R.R. next to lobby, E. side.
2) Painted upright hallway, R.R. on W. side, in hallway.
3) Need more upright coverage, office, south side of bldg, in-between bullpen and O.M.
4) No upright coverage in break room, north side of bldg.
5) Blocked upright, hallway, outside conf. room, east side of bldg.
04/26/2016 FIRE SPKLR - OH PIPING & HYDRO Denied Made appt with contractor; no one on site when I arrived. Must call it in again.