Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T15BU01483
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2016 | FIRE SPKLR - OH PIPING & HYDRO | Approved | All OH/Hydro approved for this permit. All "refresh" areas already finaled/approved. |
|
08/26/2016 | FIRE SPKLR - OH PIPING & HYDRO | Denied | DENIED. Gauge 175psi. Did not look at any OH. | |
08/25/2016 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1. Sprinkler pipe leaking in hallway. 2. Pressure at 170psi on arrival. |
|
08/11/2016 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | OH for restrooms and hall to restrooms. Will add bracket, north restroom. | |
05/20/2016 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | PA No OH or Hydro approved or needed on this section. This is for the Operating room only. All existing. C-Section 01, 11051, This section approved/finaled, TCO approved for this area/room. |
|
05/19/2016 | FIRE SPKLR - OH PIPING & HYDRO | Denied | No approved plans on site; could not access panels above ceiling on side where pipe was replaced - painted over panels accessed panels on other side of the new light - found upright wrapped in towel. Contractor took it off. |