Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
02/11/2016 FIRE SPKLR - FINAL Approved
02/01/2016 FIRE SPKLR - FINAL Partial Approval Passed -Flow Test - alarm in 47 sec ( outside bell at 25 sec)
Passed -2 inch main drain test - static was 80 psi, dropped to 75 psi, required is 48.4 psi.

PARTIAL APPROVAL:
1. Waiting for appeal to be approved for no heads added to the bottom of the elevator shaft.
2. bathroom stall-door frame is blocking the spray pattern of the head that is located on the bottom of the soffit in the womens downstairs restroom.