Permit: T15BU01452

Parcel: 138220790

Inspection Status: Closed

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
10/12/2022 FIRE - ALARM FINAL Closed PERMIT CLOSED CONTRACTOR DIDN'T CALL IN INSPECTION.
06/17/2016 FIRE - ALARM FINAL Partial Approval Acceptance test approved however still need the following:
1) Horn/strobes cannot say "fire."
2) Need lockout on breaker.
3) Need 704 diamond on exterior doors. Front and rear.
4) Need CO2 warning sign on pump room and tank rooms. See nfpa 55, 13.6.3.1 for specs and verbiage.
5) Need CO2 detector in pump room.