Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2015 | FIRE SPKLR - OH PIPING & HYDRO | Approved | Heads added in soffit and upstairs in concealed space around ventilation duct work. May close up hard lid and sheet rock. |
|
| 12/23/2015 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1. Need head in Vent box made of combustible construction - particle board ( upstairs around 2 vents from roof) 2. Insufficient coverage on far right side of soffit, far left side of soffit and inbetween heads in soffit due to duct work. |