Permit: T15BU01447

Parcel: 13507444E

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T15BU01447

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
12/30/2015 FIRE SPKLR - OH PIPING & HYDRO Approved Heads added in soffit and upstairs in concealed space around ventilation duct work.
May close up hard lid and sheet rock.
12/23/2015 FIRE SPKLR - OH PIPING & HYDRO Denied 1. Need head in Vent box made of combustible construction - particle board ( upstairs around 2 vents from roof)
2. Insufficient coverage on far right side of soffit, far left side of soffit and inbetween heads in soffit due to duct work.