Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T15BU01362
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2016 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
| 04/11/2016 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1. wrong nozzle over charbroiler ( 230 instead of 1 N) 2. 3 "1 W " nozzles in plenum pointing down ( plans show 2 "1 N" nozzles pointing from left to right side of plenum 3. pull station is a 58 inches high 4. Gas valve is 2 ", not 1 1/2" inch like on plans 5. K extinguisher last tested in 2014 6. no test performed on system until correct nozzles placed and back of cooking appliances and wall behind are clean and free of grease build up. |