Permit: T15BU01362

Parcel: 11451142A

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T15BU01362

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2016 FIRE - KITCHEN EXH HOOD FINAL Approved
04/11/2016 FIRE - KITCHEN EXH HOOD FINAL Denied 1. wrong nozzle over charbroiler ( 230 instead of 1 N)
2. 3 "1 W " nozzles in plenum pointing down ( plans show 2 "1 N" nozzles pointing from left to right side of plenum
3. pull station is a 58 inches high
4. Gas valve is 2 ", not 1 1/2" inch like on plans
5. K extinguisher last tested in 2014
6. no test performed on system until correct nozzles placed and back of cooking appliances and wall behind are clean and free of grease build up.