Permit: T15BU01361

Parcel: 13606002C


Addresses:

8800 E 22ND ST 01


Inspection Status: Approved

Inspection History: FIRE SPKLR - UG PIPING FLUSH

Permit Number - T15BU01361

Inspection Description - FIRE SPKLR - UG PIPING FLUSH

Inspection Status - Approved

Date Description Inspector Results Comments
12/02/2015 FIRE SPKLR - UG PIPING FLUSH Approved
12/01/2015 FIRE SPKLR - UG PIPING FLUSH Denied Piping wraped OKAY to bury
11/30/2015 FIRE SPKLR - UG PIPING FLUSH Denied Need to wrap all ductile pipe and mechanical joint fittings with 10ml plastic and 10 ml tape no exposed metal to ground.
Fire inspector will need see wrapped metal parts before burying the trench.