Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T15BU01361
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | 200 psi for 2 hours approved Wire tracer is in place Need to wrap all ductile pipe and mechanical joint fittings with 10ml plastic and 10 ml tape no exposed metal to ground. |