Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | 200 psi for 2 hours approved Wire tracer is in place Need to wrap all ductile pipe and mechanical joint fittings with 10ml plastic and 10 ml tape no exposed metal to ground. |