Inspection History: FIRE SPKLR - FINAL
Permit Number - T15BU01239
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2015 | FIRE SPKLR - FINAL | Approved | ||
12/01/2015 | FIRE SPKLR - FINAL | Partial Approval | upright in ceiling exposed to pendant in riser room. Need to either place ceiling or removed pendant in riser room. ceiling upright will reach, but needs to have insulation secured so as not to hang over uprights. 2. place menu board so two sprinklers are not too close. 3. as builds shall reflect extra head in prep area near the freezer. |