Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T15BU01198

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
03/07/2016 FIRE SPKLR - UG, PIPING, HYDRO Approved
02/17/2016 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval UG hydro/piping approved for FS1 and FS2 (see plans).
01/13/2016 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval FS3 ( see plans) from where city will tie in up to stub up - was pressured up since yesterday at 200 lbs. read at 9 am - 220 lbs.
All pipes/connections as per approved plans. May back fill this section. Still need to lay FS
01/12/2016 FIRE SPKLR - UG, PIPING, HYDRO Not ready for Inspection On site at 9 am; was only pressured up for 1 hr.
01/11/2016 FIRE SPKLR - UG, PIPING, HYDRO Denied 1.Was not pressured up
2.pipe has already been backfilled from city connection for about 10 feet but then exposed at the next joint before the stub up. Bell is secured properly ( with stabalizer) and stub up is in thrust block.