Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T15BU01198
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | ||
| 02/17/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | UG hydro/piping approved for FS1 and FS2 (see plans). | |
| 01/13/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | FS3 ( see plans) from where city will tie in up to stub up - was pressured up since yesterday at 200 lbs. read at 9 am - 220 lbs. All pipes/connections as per approved plans. May back fill this section. Still need to lay FS |
|
| 01/12/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Not ready for Inspection | On site at 9 am; was only pressured up for 1 hr. | |