Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2016 | FIRE - ALARM FINAL | Approved | ||
| 08/15/2016 | FIRE - ALARM FINAL | Partial Approval | Must test all duct detectors or 10 % with an approved record of test and balances. Need to connect 2 fans to alarm system ( cfm over 2000), must automatically shut down. |