Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T15BU01157

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2015 FIRE - KITCHEN EXH HOOD FINAL Approved Passed link cut test.
10/20/2015 FIRE - KITCHEN EXH HOOD FINAL Partial Approval Partial Approval- Failed Link test due to grease in the line made too slow of a system response.

Ever other test on the system has passed. Cartridge test, gas shut down, sounded alarm system and reported to main panel; signal was sent to Central Alarm. All nozzles are per plan, distances from appliances are correct and correctly aimed.
NS 10/20/15
10/13/2015 FIRE - KITCHEN EXH HOOD FINAL Denied hood system is connected to the entire building fire alarm system and no one had notified occupants or building management of hood system test. Will reschedule after coordinating with the building management 48 hrs in advance to avoid dumping the entire building for a hood system test.
Exhaust fans were wired improperly according to Cintas and were turning off when the microswitch was tripped. .