Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T15BU01157
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2015 | FIRE - KITCHEN EXH HOOD FINAL | Approved | Passed link cut test. | |
10/20/2015 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | Partial Approval- Failed Link test due to grease in the line made too slow of a system response. Ever other test on the system has passed. Cartridge test, gas shut down, sounded alarm system and reported to main panel; signal was sent to Central Alarm. All nozzles are per plan, distances from appliances are correct and correctly aimed. NS 10/20/15 |
|
10/13/2015 | FIRE - KITCHEN EXH HOOD FINAL | Denied | hood system is connected to the entire building fire alarm system and no one had notified occupants or building management of hood system test. Will reschedule after coordinating with the building management 48 hrs in advance to avoid dumping the entire building for a hood system test. Exhaust fans were wired improperly according to Cintas and were turning off when the microswitch was tripped. . |