Permit: T15BU01116

Parcel: 13323193C


Addresses:

750 N KOLB RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
10/01/2015 FIRE SPKLR - UG, PIPING, HYDRO Approved
09/30/2015 FIRE SPKLR - UG, PIPING, HYDRO Denied 1. Need to hydro at 200psi for 2 hours.
2. Contractor only pumped up to 150psi.
3. Okay to backfill.
4. Verified tracer wire and wrapped restraints.