Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T15BU01056
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2016 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
02/04/2016 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Missing Snoot on end of 3 Inch check valve ( part of FDC). - noticed while out on a fire alarm final. | |
12/11/2015 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | need upright over hood ( center) need upright over bathroom ( confirmed by pic today - may put in hard lid) need upright in spot blocked by ventilation ALL ON THE PLANS passed hydro - 210 psi @ 1:35 pm was charged up 10:00 am |