Permit: T15BU01044

Parcel: 14029014A


Addresses:

3381 E GLOBAL LP

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
09/24/2015 FIRE SPKLR - OH PIPING & HYDRO Approved
09/23/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval First Floor
1.Did not pass pressure test - retest
2. remove head too close to new head on existing line in middle where connection will be made
3. remove head too close to new head on existing line at corner near exit door (SW corner)?

Second Floor
4. Rack on Wall ( South Wall /west side) needs in rack head ( see plans for note

Third Floor
5. Did not pass pressure test
6. remove head too close to new head on existing line at corner near exit door (SW corner)?