Permit: T15BU00989

Parcel: 13606002C


Addresses:

8800 E 22ND ST 01


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T15BU00989

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2016 FIRE SPKLR - FINAL Approved
12/08/2015 FIRE SPKLR - FINAL Denied 1. Install a sign above FDC showing the location from the parking lot north side sign shall have red FDC letters 6 inch in size on a white background all reflective.
2. Correct sprinkler coverage in the exiting mechanical room's heads to far from deck
3. In 2nd floor corridor north side top of stairs move sidewall head 4 inches away from wall with door that was installed.
4. Correct sprinkler coverage in chase exposed room for bathrooms one head blocked by piping.
5. Need to have sprinkler system monitored on the fire alarm system (flow switch and tamper switch on main valve).
6. Need outside fire bell for sprinkler system
7. Need to sign valves on riser
8. Need sidewall head in spare head box
9. Need to patch all holes in walls and ceilings in mechanical rooms and janitors rooms