Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T15BU00989
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2016 | FIRE SPKLR - FINAL | Approved | ||
12/08/2015 | FIRE SPKLR - FINAL | Denied | 1. Install a sign above FDC showing the location from the parking lot north side sign shall have red FDC letters 6 inch in size on a white background all reflective. 2. Correct sprinkler coverage in the exiting mechanical room's heads to far from deck 3. In 2nd floor corridor north side top of stairs move sidewall head 4 inches away from wall with door that was installed. 4. Correct sprinkler coverage in chase exposed room for bathrooms one head blocked by piping. 5. Need to have sprinkler system monitored on the fire alarm system (flow switch and tamper switch on main valve). 6. Need outside fire bell for sprinkler system 7. Need to sign valves on riser 8. Need sidewall head in spare head box 9. Need to patch all holes in walls and ceilings in mechanical rooms and janitors rooms |