Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T15BU00989
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2016 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
12/31/2015 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | - Still need FDC sign posted high on wall near electric Bell - 12 inch Letters, Red letters on White background. - Flow and Tamper signals were received - flow switch set at 31 seconds pressure before main drain test at 75 dropped to 70 ( fluctuated between 70-73) need to patch holes and walls in celing and walls in janitors closet. |
|
12/08/2015 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 240 PSI FOR 2 HOURS APPROVED 1. Install a sign above FDC showing the location from the parking lot north side sign shall have red FDC letters 6 inch in size on a white background all reflective. 2. Correct sprinkler coverage in the exiting mechanical room's heads to far from deck 3. In 2nd floor corridor north side top of stairs move sidewall head 4 inches away from wall with door that was installed. 4. Correct sprinkler coverage in chase exposed room for bathrooms one head blocked by piping. 5. Need to have sprinkler system monitored on the fire alarm system (flow switch and tamper switch on main valve). 6. Need outside fire bell for sprinkler system 7. Need to sign valves on riser 8. Need sidewall head in spare head box 9. Need to patch all holes in walls and ceilings in mechanical rooms and janitors rooms |
|
11/10/2015 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1. No one on site 2. No permit for underground has been pulled 3. Underground is not up to NFPA 24 standard ( pipe is not listed and does not meet the standards for C-900. 4. No thrust block where underground drops 5 feet to city tie in. |
|
10/09/2015 | FIRE SPKLR - OH PIPING & HYDRO | Not ready for Inspection | ARRIVED @ 4:00. NO ONE ON JOB SITE. |