Permit: T15BU00947

Parcel: 14118634A


Addresses:

10146 E OLD VAIL RD

Inspection Status: Partial Approval

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
11/23/2015 FIRE - ALARM FINAL Partial Approval alarm system itself has been tested and approved, however can not give final until as-builds are submitted.
11/13/2015 FIRE - ALARM FINAL Partial Approval Need to test for correct signals. All ducts tested, roof top airhandler duct tested, smokes tested.- all passed. The only problem was that the signals were not sent correctly to the monitoring system. Need to make sure that
smoke, pull, flow are alarms
ducts and tamper are supervisory
smoke disconected, elec out, battery dc are trouble
dont need to test every smoke and duct detector - this has already been done.