Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2015 | FIRE - ALARM FINAL | Partial Approval | alarm system itself has been tested and approved, however can not give final until as-builds are submitted. | |
| 11/13/2015 | FIRE - ALARM FINAL | Partial Approval | Need to test for correct signals. All ducts tested, roof top airhandler duct tested, smokes tested.- all passed. The only problem was that the signals were not sent correctly to the monitoring system. Need to make sure that smoke, pull, flow are alarms ducts and tamper are supervisory smoke disconected, elec out, battery dc are trouble dont need to test every smoke and duct detector - this has already been done. |